-
Notifications
You must be signed in to change notification settings - Fork 632
New issue
Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.
By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.
Already on GitHub? Sign in to your account
Add schleifenbauer PDU #1217
base: main
Are you sure you want to change the base?
Add schleifenbauer PDU #1217
Conversation
Hi @Wqrld, could you please provide the updated generator/generator.yml and add the needed mib files for this to work to the Makefile? |
The generator was also failing locally before adding my patch because of 404's, i had to rip those out of the makefile to generate this configuration. |
I do not have the rights to those original mib files so i'm not sure if i'm allowed to add them. They were taken from https://docs.schleifenbauer.eu/?dir=Interfaces/SNMP |
Shouldn't be an issue to curl their public available mib files in the generator/Makefile |
Signed-off-by: Luc H <[email protected]>
Signed-off-by: Luc H <[email protected]>
$(eval TMP := $(shell mktemp)) | ||
@echo ">> Downloading schleifenbauer to $(TMP)" | ||
@curl $(CURL_OPTS) -o $(TMP) $(SCHLEIFENBAUER_URL) | ||
@unzip -j -d $(MIBDIR) $(TMP) SCHLEIFENBAUER-PRODUCTS-MIB.txt SCHLEIFENBAUER-DATABUS-MIB.txt SCHLEIFENBAUER-SMI.txt |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
The SCHLEIFENBAUER-PRODUCTS-MIB.txt seems not to be included in this zipfile, only in the older https://docs.schleifenbauer.eu/Interfaces/SNMP/PDU_mib_244.zip. If the file is necessary we'd need to get it from the 2nd zipfile.
Signed-off-by: Luc H <[email protected]>
# https://docs.schleifenbauer.eu/?dir=Interfaces/SNMP | ||
schleifenbauer: | ||
walk: | ||
- 1.3.6.1.4.1.31034.12 |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
This OID is overly broad. I think we want to be more targeted here with which walks to include. Some of the metrics included by this are read-write settings OIDs that have no meaning as metrics.
Let's start with the most useful part, the device table.
- 1.3.6.1.4.1.31034.12 | |
- sdbMgmtCtrlDevicesTable |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I think almost everything in 1.3.6.1.4.1.31034.12.1.1.2 would be of use, which is basically the whole generated list. There are a few you could leave out, but for my usecase more is better.
This patch adds support for Power Distribution Units from https://www.schleifenbauer.eu
I was able to successfully read out my PDU's into grafana. I hope this may be useful for others too.
Note:
This query takes about one minute to run on my device, running into timeouts. Adding
fixes this. I think this is an issue with many SNMP devices, so it might be an idea to add statements like these (with lower limits) to the readme example.